DuraLife® Dual-Rated CIC/CI Cables
UL 2196 2-Hour Fire Resistive Cable FPLR Shielded / Unshielded 105°C/300V
Certified to the harsh requirements of the UL2196 Test for Fire Resistive Cables, the
DuraLife Dual-Rated CIC/CI cables ensure two-hour operation of critical systems in
the event of a fire. The dual rating design offers the most versatility in meeting code
survivability requirements in both in-conduit and free air installation scenarios.
Description: Dual-Rated CIC/CI Cable. UL/CAN (ULC) 2196 Certified/UL 1424 Listed. FHIT/
FHIT7 (ULC) System No. 28C. Low smoke, zero halogen design (LSZH).
Sizes Available: 2 conductor, 18-12 AWG unshielded; 18-14 AWG shielded.
Construction:
- Conductor: Oxygen-free bare copper (OFHC), solid and/or stranded
- Insulation: Proprietary ceramifiable silicone rubber
- Assembly: Color-coded black/red leads, 3 twists/foot
- Jacket: Red low smoke/zero halogen FRPE with sequential footage markers (custom colors available/special order mins apply)
Applications:
- Hospitals & Healthcare Facilities
- High Rise & Mix Use Buildings
- Universities & College Campuses
- Stadiums, Casinos, Places of Assembly
- Transit Bridges, Tunnels and Subways
- Government Facilities
Critical Systems:
- Fire Alarm and EVAC Systems
- Smoke Evacuation and Control
- Fan & Pressurization Systems
- Strobes & Notification Appliances
- Area of Refuge Systems
- Emergency Lighting
COMPLIANCE:
- UL 1424 Listed FPLR/FPLR-CI (dual-rated) for Power-Limited Fire Alarm Circuits. Riser Rated. 300V/105°C classified
- UL / CAN (ULC formerly S-139) Certified to UL 2196 2-hour fire rating in FHIT / FHIT7 28C
- CSA Certified FAS90; CSA Std. C22.2 No. 208-14 FT4-ST1
- UL Certified 2-hour fire rating as FPLR-CI for Free Air installed per NEC code
- UL 444 Listed “CMR/CMR-CI” as Communications Cable
- Fire alarm circuit integrity, emergency systems, and healthcare facilities (NEC Articles 760, 700 & 517)
- Meets National Fire Protection Code (NFPA 70 & 72) fire alarm survivability circuit requirements
- Meets National Fire Protection Code (NFPA 130 & 502) fire alarm survivability circuit requirements
- Compliance tested to UL 1424 as suitable for use in applications requiring wet rating
- Meets UL1685 and FT4/IEEE 1202 requirements
- Tested for Sunlight Resistance in compliance with UL 2556 requirements
- Suitable for 2-hour certified fire-resistive applications in EMT, IMC, or Phenolic conduit systems
- UL Listed File No. E-241484. UL Fire Directory R-21213
- Splice Allowance
- Performance testing of cables, cold bend test of complete cable per defined testing parameters and UL 1424
- NYC certified and CAFM approved
HARDWARE & ACCESSORIES CERTIFIED: (Refer to DuraLife® II Installation Instructions/ Phenolic Addendum for details)
- EMT/IMC Conduit: Wheatland/Western Tube
- EMT/IMC Conduit: Allied/Columbia (EMT: E-Z Pull Brand)
- Phenolic Conduit: Champion Fiberglass
- EMT/IMC Compression Couplings: Hubbell/Raco
- EMT/IMC Set-Screw Coupling: Hubbell/Raco
- Phenolic Coupling: Champion Fiberglass
- NEMA 1 Splice Enclosure/Pull Box: Eaton/Cooper (system use only)
- Standard UL listed steel 4/S Utility Box (CI only)
- Expansion Couplers: Bridgeport fittings (EMT/IMC)
- Box Fittings: Compression – Cooper Crouse-Hinds (EMT); Hubbell/Raco (EMT/IMC) Set Screw – Hubbell/Raco (EMT/IMC) Phenolic – Champion Fiberglass
- Conduit Clamps: Erico (Phenolic conduit only)
- Splice Connector: 3M Butt-Type Crimp Terminals
- Splice Tapes – 1”: 3M Silicone; St. Gobain Fiberglass Tape
- Pulling Lubricant: Polywater LZ
SPECIFICATIONS
DuraLife® Dual-Rated CIC/CI Cables
UL 2196 2-Hour Fire Resistive Cable FPLR Shielded / Unshielded 105°C/300V
Download DuraLife® Dual Rated CIC/CI Cable Specs
UNSHIELDED
RADIX WIRE-II DURALIFE-IITM E241484 2/C #AWG FPLR/FPLR-CI/CMR 300V/105C / (UL) 2196 (ULC) 2-HR FIRE RESISTIVE CABLE FOR USE IN FHIT/FHIT7 ELECTRIC CIRCUIT INTEGRITY SYSTEM #28C. SEE UL FIRE RESISTANCE DIRECTORY R21213 // CSA LL13427 FAS90 300V FT4-ST1 Sun Res Wet (MONTH/YEAR) CI – NYC certified fire alarm cable (XXXX FT)
| RADIX P/N | #COND | AWG | SOLID OR STRANDED | NOMINAL O.D. (INCH) | NET WEIGHT (LBS PER MFT) | RESISTANCE (OHMs/MFT) | NOMINAL CAPACITANCE (pF/FT) |
|---|---|---|---|---|---|---|---|
| CTU18A0102 | 2 | 18 | Solid | 0.305 | 53 | 6.48 | 14.4 |
| CTU16A0102 | 2 | 16 | Solid | 0.335 | 62 | 3.99 | 15.3 |
| CTU16A0702 | 2 | 16 | Stranded | 0.335 | 62 | 4.02 | 15.6 |
| CTU14A0102 | 2 | 14 | Solid | 0.344 | 77 | 2.57 | 17.1 |
| CTU14A0702 | 2 | 14 | Stranded | 0.350 | 77 | 2.60 | 17.3 |
| CTU12A0102 | 2 | 12 | Solid | 0.392 | 98 | 1.61 | 17.4 |
| CTU12A0702 | 2 | 12 | Stranded | 0.392 | 98 | 1.64 | 17.6 |
SHIELDED
RADIX WIRE-II DURALIFE-IITM E241484 2/C #AWG FPLR/FPLR-CI/CMR/SHLD 300V/105C / (UL) 2196 (ULC) 2-HR FIRE RESISTIVE CABLE FOR USE IN FHIT/FHIT7 ELECTRIC CIRCUIT INTEGRITY SYSTEM #28C. SEE UL FIRE RESISTANCE DIRECTORY R21213 // CSA LL13427 FAS90 300V FT4-ST1 Sun Res Wet (MONTH/YEAR) CI – NYC certified fire alarm cable (XXXX FT)
| RADIX P/N | #COND | AWG | SOLID OR STRANDED | NOMINAL O.D. (INCH) | NET WEIGHT (LBS PER MFT) | RESISTANCE (OHMs/MFT) | NOMINAL CAPACITANCE (pF/FT) |
|---|---|---|---|---|---|---|---|
| CTS18A0102 | 2 | 18 | Solid | 0.335 | 55 | 6.48 | 18.4 |
| CTS16A0102 | 2 | 16 | Solid | 0.360 | 65 | 3.99 | 19.1 |
| CTS16A0702 | 2 | 16 | Stranded | 0.360 | 65 | 4.02 | 19.4 |
| CTS14A0102 | 2 | 14 | Solid | 0.390 | 79 | 2.57 | 21.4 |
| CTS14A0702 | 2 | 14 | Stranded | 0.393 | 79 | 2.60 | 21.7 |
System Fill Allowances (EMT – 1/2″ to 2″; IMC – 3/4″ to 2″)
| EMT/IMC | ½” | ¾” | 1″ | 1 ¼” | 1 ½” | 2″ |
|---|---|---|---|---|---|---|
| Part No. | No. of Cables Max Fill | |||||
| CTU18A0102 | 1 | 2 | 4 | 6 | 10 | N/A |
| CTU16A0102 | 1 | 1 | 3 | 5 | 7 | 10 |
| CTU14A0102 | 1 | 1 | 3 | 5 | 7 | 10 |
| CTU12A0102 | 1 | 1 | 2 | 4 | 5 | 10V/9H |
| CTS18A0102 | 1 | 1 | 3 | 5 | 8 | N/A |
| CTS16A0102 | 1 | 1 | 3 | 5 | 7 | 10 |
| CTS14A0102 | N/A | 1 | 2 | 4 | 6 | 10 |
System Fill Allowances (Phenolic Conduit – 1″ to 2″)
| PHENOLIC | 1″ | 1 ¼” | 1 ½” | 2″ | ||
|---|---|---|---|---|---|---|
| Part No. | No. of Cables Max Fill | |||||
| CTU18A0102 | 3 | 6 | 9 | N/A | ||
| CTU16A0102 | 2 | 4 | 6 | 10 | ||
| CTU14A0102 | 3 | 5 | 7 | 10 | ||
| CTU12A0102 | 2 | 4 | 5 | 10V/9H | ||
| CTS18A0102 | 3 | 5 | 7 | N/A | ||
| CTS16A0102 | 2 | 4 | 6 | 10 | ||
| CTS14A0102 | 2 | 4 | 6 | 10 | ||